TA6000

Integrated system

TA6000.

Battery and inverter in one cabinet, with PV input connectivity and three specified storage configurations. AC output options depend on the selected configuration.

INVERTER
Included
ENCLOSURE
Not specified
NOMINAL ENERGY
10.24–20.48 kWh
AC CONFIGURATION
120 V US / 230 V EU AC options
Start your project ↗

Specifications

Model / configurationEnergy (kWh)AC options (kW)
TA6000-M210.246–10
TA6000-M315.366–12
TA6000-M420.486–12

Specify the correct market AC voltage and 50 / 60 Hz option. PV input: 11 kW for M2; 11–13.2 kW for M3/M4. No three-phase or split-phase capability is claimed.

ModelDimensions (mm)Approx. kg
TA6000-M2590 × 570 × 1880 / W × D × H244
TA6000-M3590 × 570 × 1880 / W × D × H286
TA6000-M4590 × 570 × 1880 / W × D × H328

Communication: RS485 / RS232 / CAN / Wi-Fi; Bluetooth optional
Temperature: Operating −20 to 60 °C

Plan for the room through every season.

UK conditions vary with region, elevation and exposure; the Met Office distinguishes generally warmer, drier conditions in the south and east from those farther north and west. The proposed equipment room needs a separate assessment.

Temperature:
Operating −20 to 60 °C
ENCLOSURE
Not specified
01

Cooler winter location · unheated garage or outbuilding

An unheated garage in a colder or more exposed location can behave differently from a room within the occupied home. Use the actual expected temperature at the unit.

Check charging limits before selecting the location. TR Pro lists charging 0 to 55 °C and discharging −20 to 60 °C. Confirm any optional heating and charging protection; the lower discharge limit is not permission for subzero charging. HP Ultra limits must be confirmed for its exact configuration.

Can the battery position fall below 0 °C during charging?
  • Is any heating option included and confirmed for this model?
  • Can cold surfaces develop condensation as conditions change?
02

Detached or terraced home · dedicated utility space

Available floor area, access routes and separation from everyday storage matter when planning a dedicated equipment area in an existing home.

EU all-in-one combines battery and inverter in an IP21 enclosure and needs no extra inverter. Battery-only families need an external compatible inverter. Assess the exact manual's access, ventilation, mounting and project-specific placement requirements before choosing the room.

Can the proposed area be kept dry and clear for service?
  • Will access and required cooling space remain available?
  • Is this a new integrated installation or a battery addition to an existing inverter?
03

Seasonal damp or summer heat · assess the building

Regional climate is a starting point. A damp ancillary room or a sun-heated enclosed space can have conditions unlike nearby occupied rooms.

Record both the lowest and highest room temperatures, condensation and water-entry risks. IP66 does not on its own establish condensation, flood or coastal salt-spray suitability. Confirm enclosure, cooling and any high-temperature derating for the exact selected equipment.

Is there damp, a water-entry route or coastal exposure?
  • Does summer sun or roof heat raise the equipment-room temperature?
  • What placement and output limits apply to the exact configuration?
Specifications
  • Choose the architecture first: EU and TA6000 include an inverter. Battery-only TR, HP and TB families require a compatible external inverter with confirmed voltage, current and communication settings.
  • Check charging and discharging limits separately. Optional heating and a general operating-temperature field do not establish universal subzero charging; a maximum temperature does not promise full output at that temperature.
  • Use the exact enclosure rating and placement instructions. IP21, IP20, optional IP54 and IP66 are different source ratings; none alone establishes resistance to condensation, flooding or coastal salt spray.

PRODUCT DETAIL / ORIGINAL LITERATURE

Every side. Every connection.

The supplied brochure provides two labelled connection/breaker insets and internal cabinet/cell illustrations on printed pages 15-16. Crops avoid visible product logos without AI editing, repainting, or invented structure. Embedded views not visibly matched to the printed product page were excluded. These views do not establish pinouts, cable sizes, commissioning steps or installation compatibility.

Original terminal labels
Original terminal labelsConnection panel labelled for load, grid, optional generator, PV and communication.
Terminal panel close-up
Terminal panel close-upClose-up of the cabinet terminal panel.
Original breaker labels
Original breaker labelsBattery, PV1, PV2, load and grid breakers in the illustrated compartment.
Breaker compartment close-up
Breaker compartment close-upCircuit breakers within the cabinet's breaker compartment.
Upper cabinet and service bay
Upper cabinet and service bayUpper cabinet compartment with the inverter and connection area.
Cell assembly detail
Cell assembly detailBattery cell tops in a partial internal illustration.

Know your interfaces.

Power connections

Load Output
Output position identified as Load Output in the brochure.
Grid Input
Connection position identified as Grid Input.
Generator Input (optional)
The generator input is explicitly marked optional in the original callout.
PV Input
PV connection area identified by the original callout.
PV1 Input Breaker
Breaker identified for PV1 Input.
PV2 Input Breaker
Breaker identified for PV2 Input.

Communication

Communication Port
Connection area labelled Communication Port. No protocol pin assignments are specified in this component view.

Controls & indicators

Battery Breaker
Breaker labelled for the battery section.
Load Breaker
Breaker identified for the load connection.
Grid Breaker
Breaker identified for the grid connection.

Source: Residential ESS brochure · PDF page 8 · printed pages 15-16